Main Feed Cable Specification

Note:
codes. For UL 924 emergency installation, secure an emergency power source for
control power and line feeds as required.
Purpose and Type
Main Lugs 120/240V 1Ø
Main Lugs 120/208V 3Ø
Main Lugs 277/480V 3Ø
Main Circuit Breaker 120V/240
1Ø, 100A, 22kA
Main Circuit Breaker 120V/240
1Ø, 200A, 22kA
Main Circuit Breaker
120/208V 3Ø, 200A,10kA
Main Circuit Breaker
120/208V 3Ø, 200A, 22kA
Main Circuit Breaker
120/208V 3Ø, 200A, 42kA
Main Circuit Breaker
120/208V 3Ø, 100A, 10kA
Main Circuit Breaker
277/480V 3Ø, 200A, 14kA
Main Circuit Breaker
277/480V 3Ø, 200A, 65kA
Main Circuit Breaker
277/480V 3Ø, 150A, 14kA
Ground Input Lug
(all models)
1. With the conduit in place, make sure the upstream source of power is off or isolated, then
pull the incoming power cables, phase, neutral and ground, to the panel. Refer to the wire
specification chart above for wire, strip length, torque and tool specification.
2. Strip back the cable jackets to the length indicated in the wire specification chart,
depending on the connection.
3. Terminate the ground cable to the ground lug located on the top left or top right side of
the panel.
Using a 5/16 inch hex key, tighten the lug to the torque indicated above.
4. Terminate the neutral cable to the neutral lug located on the right side of the panel.
Using a 5/16 inch hex key, tighten the lug to the torque indicated above.
5. Terminate the phase cables to the main lugs or main circuit breaker (if installed). Using the
appropriate sized Allen wrench, tighten the lug to the torque indicated above.
Installation
It is the installing contractor's responsibility to comply with all local electrical
Wire Range
2
25–150 mm
(4 AWG–300kcmil)
2
50–150 mm
(1 AWG–300kcmil)
2
50–150 mm
(1 AWG–300kcmil)
2
95–150 mm
(3/0–
300kcmil)
2
10–95 mm
(8 AWG–3/0)
2
16–185 mm
(6 AWG–350kcmil)
2
25–150 mm
(4 AWG–300kcmil)
Strip
Torque (lb-in)
length
20 mm
28 Nm
(0.8 in)
(250 in-lb)
20 mm
28 Nm
(0.8 in)
(250 in-lb)
20 mm
28 Nm
(0.8 in)
(250 in-lb)
20 mm
28 Nm
(0.8 in)
(250 in-lb)
0.8"
5.6 Nm
(20 mm)
(50 in-lb)
6–1 AWG: 
13.5 Nm
(120 in-lb)
0.9"
(23 mm)
1/0–350 kcmil: 
31 Nm
(275 in-lb)
20 mm
31 Nm
(0.8 in)
(275 in-lb)
Wrench/
Driver
5/16 in
5/16 in
5/16 in
5/16 in
flatblade
5/16 in
5/16 in
22