Install Option Cards

Option cards, including the 0–10V Dimming Control card, DALI Control, Contact Input option
card, and the Ride-Thru Option card are available for field installation into the Relay Panel
Mains Feed. Installation instructions for each card are provided in the appendix of this manual.

Connect Data Wiring

The Relay Panel Mains Feed termination board is located at the bottom of the panel.
Termination options include:
DMX In and DMX Pass-Thru: Connects the panel to a DMX512 control source. See
and Control Wire Specification on the next page
Emergency In and Emergency Out (Panic): Allows override of the lighting control for
specified loads by emergency systems, such as a fire alarm system.
ERP-CI: Card edge connector available for connection of the optional Contact Input Card
(optional). The contact input connections allow simple, direct control of relays using a dry
contact closure.
ERP-LVD or ERP-DALI: Card edge connector available for connection of either a 0–10V
Dimming option card or DALI Control card.
Installation
.
Data
28