Connect Load Wiring
In fully loaded relay panels, all breaker to relay wiring connections are pre-terminated at the
factory. Load terminations are made to the output side of the relay card.
Load Cable Specification
Purpose and Type
Load to relay and
dimmer output
Load to ground (all
models)
Neutral bars 120 V
models
Load to neutral bars
240/277 V models
Circuit breaker
output
Relay and dimmer
card input (from
circuit breaker)
Note:
Prepare enough cable length to pull the load hot wire to the relays and
neutral and ground wires to the top of the panel.
WARNING:
breakers prior to proceeding with wiring.
23
Wire Range
12.7 mm
2
.50–16 mm
(1/2 in)
(20–6 AWG)
12.7 mm
2
2.5–25 mm
(1/2 in)
(14–4 AWG)
Small hole:
2
2.5–25 mm
(14–6 AWG)
12.7 mm
Large hole:
(1/2 in)
2
20–50 mm
(3–1/0 AWG)
10 mm
2
6 mm
(10 AWG)
(3/8 in)
12.7 mm
2
6 mm
(10 AWG)
(1/2 in)
RISK OF ELECTRIC SHOCK! Check power is OFF to the circuit
Strip
Torque (lb/in)
length
15.6 in-lb (1.8 Nm)
2
2.5–6 mm
(14-10 AWG)
2
10 mm
(8 AWG)
2
10–16 mm
(6–4 AWG)
2
2.5–6 mm
(14-10 AWG)
2
10 mm
(8 AWG)
10–16 mm2
(6–4 AWG)
2
50 mm
(1/0 AWG)
25 in-lb (2.8 Nm)
15.6 in-lb (1.8 Nm)
2.3 Nm
(20 in-lb)
2.8 Nm
(25 in-lb)
4.0 Nm
(35 in-lb)
2.3 Nm
(20 in-lb)
2.8 Nm
(25 in-lb)
4.0 Nm
(35 in-lb)
5.6 Nm
(50 in-lb)
Relay Panel Mains Feed Installation Manual
Driver
flatblade
flatblade
flatblade
flatblade
flatblade