Chapter 3
Final Installation and Power Up
Verify Installation
Check that the panel is securely mounted with all mounting hardware tight.
•
Remove all metal shavings and debris from the unit.
•
Is there sufficient clearance in the front of the unit for door access?
•
Check wiring:
•
Are all load wires terminated to the correct module? See
-
page 23
Are all load circuits free of short circuits?
-
Do all control cables meet specifications? See
-
page 29
Are all low-voltage control cables routed separately from high voltage cables?
-
Are all data terminations terminated? See
-
Check that each relay is fully seated by pressing down on each relay near the center of the
•
panel. Also check that all fuses are fully seated.
For each module in the panel, check the factory wiring to ensure that all terminations are
•
secure.
Press down firmly on each neutral spade terminal (typically blue).
-
Neutral spade
terminal
Are all circuits properly labeled for identification by service personnel?
•
33
.
.
Load Cable Specification on
Data and Control Wire Specification on
Connect Data Wiring on page 28
Relay Panel Mains Feed Installation Manual
.