Rough-in Conduit and Cable

The Echo Relay Panel Feedthrough has removable plates located on top, bottom and both
sides to accommodate conduit fittings for line, load, and control electronics power wiring.
Remove the plates to punch conduit access as required.
1. Install conduit for line, load and control wiring to the panels in the appropriate locations.
Cable Routing and Conduit Access on page 13
See
Size conduit appropriately for the specified wire and expected loads at the panel.
Note:
codes. For UL 924 emergency installation, secure an emergency power source for
control electronic power and line feeds as required.
2. Install conduit as required for low-voltage control wiring. All low-voltage terminations are
conveniently located behind the user interface of the panel. Two 12.7 mm (1/2 in)
knockouts are provided for low-voltage control wiring access.
Note:
voltage (Class 1) wiring.
3. Pull line, load, and control wiring through installed conduit to the panel.
Individual line feeds from branch circuit breaker to relays.
Individual load wires from the relays to the lighting loads.
A dedicated circuit for control electronics power.
4. Pull low-voltage (control) wiring through the conduit to the I/O compartment knockouts.
See
Cable Routing and Conduit Access on page 13

Connect Wiring

Relays - Each relay has staggered output terminals for easy access to line and load connection.
A Phillips screwdriver and wire strippers are required for relay line and load terminations.
Control processor electronics AC input - A discrete circuit is required to power the control
processor; refer to
Terminations require only a precision flatblade screwdriver and wire strippers.
I/O terminations - All low-voltage control terminations are conveniently located behind the
user interface. Fold the user interface panel down to reveal termination points for DMX,
Network, Contact Input, 0-10V Control, and DALI control.

Connect Line and Load Wiring

ERP-FT is shipped standard with either 12, 24, or 48 relays installed. Depending on customer
requirements the relay type and quantities may vary for custom orders. Three relay types are
available for customer convenience, reference
Installation Procedure
It is the installing contractor's responsibility to comply with all local electrical
All low-voltage (Class 2) control wiring must be routed separately from high-
Cable Specification for Data and Control on page 12
.
.
Relay Specification on page 10
for details.
for specification.