Eaton 9PXM8S4K User Manual page 36

Table of Contents

Advertisement

BPM Signal Input Wire Routing
NOTE
c.
Navigate the 9PXM LCD to the forced and maintain bypass settings Input signals menu in the 9PXM
user guide (see
d.
Set both Forced Bypass and Maintain Bypass settings to Enabled and Normally open (see
Figure 23. Forced and Maintenance Bypass Screens
5.
Install the supplied wiring connectors to the UPS input control signal wires and connect to the terminals as
shown in or .
6.
When all connections have been made and checked, reinstall the bypass switch front cover using the
original screws.
7.
If floor anchor brackets were installed and not secured, install the floor bolts.
24
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
Make a note to enable Forced and Maintenance Bypass per the following step when
installation is complete and power available.
Figure 23
).
Load not powered
0.0kW
0.0kVA
Efficiency: 94%
Measurements
Control
Settings
Event Log
Fault Log
Identification
Register product
In/Out settings
Local settings
On/Off settings
Battery settings
Input Signals
Comm Settings
User Password Enable
User Password setting
Force Bypass
Dry contact setting
Enabled
Polarity
Normally open
0%
100%
19min
1EBM
Menu
Settings
Maintain Bypass
Dry contact setting
Enabled
Polarity
Normally open
Figure 23
).