Configuring Battery Settings
7 7 . . 7 7
C C o o n n f f i i g g u u r r i i n n g g B B a a t t t t e e r r y y S S e e t t t t i i n n g g s s
The following battery settings enable battery tests, alarms and enable auto mode and (see
7 7 . . 7 7 . . 1 1 A A d d v v a a n n c c e e d d B B a a t t t t e e r r y y M M a a n n a a g g e e m m e e n n t t
Advanced Battery Management (ABM) extends the life of the battery by shutting off the charger for 28 days
per ABM cycle and therefore reduces grid corrosion in the battery caused by trickle charging over long periods
of time. Disabling ABM means the battery chargers run in constant charge mode and never turn off. The
battery test period is every three ABM cycles.
NOTE
7 7 . . 7 7 . . 2 2 A A u u t t o o B B a a t t t t e e r r y y T T e e s s t t
The battery test will run only in Rest Mode and if ABM is enabled. The tests frequency can be modified. During
the test, the UPS transfers to Battery mode and discharges the batteries for 25% battery time remaining.
NOTE
The battery test may be postponed due to bad conditions, or failed if battery is not ok.
7 7 . . 7 7 . . 3 3 L L o o w w B B a a t t t t e e r r y y W W a a r r n n i i n n g g
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than
the setting capacity threshold (0% by default). This threshold can be modified.
7 7 . . 7 7 . . 4 4 E E x x t t e e r r n n a a l l B B a a t t t t e e r r y y S S e e t t t t i i n n g g
The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM
or in Ah.
7 7 . . 7 7 . . 5 5 D D e e e e p p D D i i s s c c h h a a r r g g e e P P r r o o t t e e c c t t i i o o n n
This setting is recommended to avoid damaging the battery. Warranty is void if deep discharge protection is
disabled
7 7 . . 8 8
R R e e t t r r i i e e v v i i n n g g t t h h e e E E v v e e n n t t L L o o g g
To retrieve the Event log through the display:
1.
Press any button to activate the menu options, then select Event log (see
2.
Scroll through the listed events.
3.
Reset event log if desired.
7 7 . . 9 9
R R e e t t r r i i e e v v i i n n g g t t h h e e F F a a u u l l t t L L o o g g
To retrieve the Fault log through the display:
1.
Press any button to activate the menu options, then select Fault log (see
2.
Scroll through the listed faults.
3.
Reset fault log if desired.
7 7 . . 1 1 0 0 C C o o n n t t r r o o l l P P a a n n e e l l O O p p e e r r a a t t i i o o n n
The control panel provides UPS function and control settings.
70
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
It is not recommended to perform a battery discharge test more often than 90 days.
Battery mode is not displayed and battery low alarm does not activate during a battery
test.
Figure 66
).
Figure 70
).
Figure 71
).