Supply voltage
Supply voltage
Residual ripple
Supply voltage range
Typical current consumption
Max. current consumption
Maximum power dissipation for nominal condition
Test section
Mechanical tests
Mechanical tests
Vibration (operation)
Vibration (storage/transport)
Shock (operation)
Conformity with EMC directives
Electromagnetic compatibility
Conducted noise emission
Interference emission
Immunity to burst
Immunity to EF
Immunity to ESD
Immunity to surge
Immunity to conducted interference
Approvals / Certificates
UL, USA
UL, Canada
Further approvals
Ordering data
Order designation
Order No.
Pcs./Pkt.
108997_en_04
5.5

FL SWITCH 2105

24 V DC (single)
3.6 V
(within the permitted voltage range)
PP
18 V DC ... 32 V DC
315 mA (at U
= 24 V DC and 25 °C ambient temperature)
S
0.5 A (At U
= 18 V DC and 60°C ambient temperature)
S
9 W (At U
= 18 V DC and 60°C ambient temperature)
S
for one minute 500 V DC
Free fall in accordance with EN 61131-2
2g, according to IEC 60068-2-6
2g, criterion 1 according to IEC 60068-2-6
30g (EN 60068-2-27)
Conformance with EMC Directive 2014/30/EU
EN 61000-6-2 EN 61000-6-3 (conducted emissions) Class B
EN 61000-6-2 EN 61000-6-3 (noise emission) Class B
EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A
EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion
A
EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B
EN 61000-6-2 EN 61000-4-5 (surge) Criterion B
EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A
UL 61010-1, Ed.3 / UL 61010-2-201, Ed.1
CSA C22.2 NO.61010-2-201:14, Ed.1 / CSA C22.2 NO.61010-
1-12, Ed.3
cULus Listed, EAC
FL SWITCH 2105
2702665