3.2.4.1

Selecting the conductors

The devices are supplied with a Push-in connector.
Observe the specifications for suitable conductors and ferrules:
Table 3-5

Selection of conductors/ferrules/screwdrivers

Conductor
Conductor cross-section, rigid, minimum
Conductor cross-section, rigid, maximum
Conductor cross-section, flexible,
minimum
Conductor cross-section, flexible,
maximum
Conductor cross-section, flexible, with
ferrule without plastic sleeve, minimum
Conductor cross-section, flexible, with
ferrule without plastic sleeve, maximum
Conductor cross-section, flexible, with
ferrule with plastic sleeve, minimum
Conductor cross-section, flexible, with
ferrule with plastic sleeve, maximum
Suitable ferrule without plastic sleeve:
maximum conductor cross-section
Suitable ferrule without plastic sleeve:
maximum conductor cross-section
Suitable screwdriver
Conductor cross-section, AWG,
minimum
Conductor cross-section, AWG,
maximum
Stripping length
Push-in
0.14 mm
1.5 mm
0.14 mm
1.5 mm
0.25 mm
1.5 mm
0.25 mm
2
0.75 mm
1.5 mm
2
0.75 mm
(color code: gray in
accordance with
DIN 46228)
Slot-headed screwdriver
Blade thickness: 0.4 mm
Blade width: 2.5 mm
Recommended: SZS 0,4X2,5 VDE,
Order No. 1205037
24
16
9 mm
Screw
2
2
2
2
2
2
2
2
0.5 mm
2
2
0.5 mm
(color code: white in
accordance with
DIN 46228)
108997_en_04