Specifications for ferrules

Recommended crimping
tool
Ferrules without insulating
collar, in accordance with
DIN 46228-1
3.2.4.2
Connecting the supply voltage
The device is operated using a 24 V DC voltage, which is applied via COMBICON connec-
tors. For the 22xx/23xx device versions, you can supply the voltage redundantly (see
Figure
37).
The module is designed exclusively for operation with safety extra-low voltage
(SELV/PELV). In redundant operation, both power supplies must satisfy the requirements
of the safety extra-low voltage.
For 22xx/23xx device versions:
If redundant power supply monitoring is active (default setting), an error is indicated if only
one voltage is applied.
A bridge between US1 and US2 prevents this error message. It is possible to deactivate
monitoring in web-based management or via SNMP.
US
GND
1 2 3 4 5
Figure 36

Operating the device with one power supply (example)

US1
US2
GND
GND
1 2 3 4 5
Figure 37

Redundant operation with two power supplies (example)

Please note that load distribution does not take place. The power supply unit with the
higher voltage will supply the device on its own.
1212034 CRIMPFOX 6
2
Cross-section: 0.25 mm
2
Cross-section: 0.34 mm
2
Cross-section: 0.5 mm
;
2
Cross-section: 0.75 mm
2
Cross-section: 1 mm
;
2
Cross-section: 1.5 mm
;
Mounting and installation
;
Length: 7 mm
;
Length: 7 mm
Length: 8 mm ... 10 mm
;
Length: 8 mm ... 10 mm
Length: 8 mm ... 10 mm
Length: 10 mm