FL SWITCH 2000 / FL NAT 2000
Conformity with EMC directives
Immunity to ESD
Immunity to surge
Immunity to conducted interference
Ordering data
Order designation
Order No.
Pcs./Pkt.
Dimensions (nominal sizes in mm)
Width
Height
Depth
Ambient conditions
Degree of protection
Protection class
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Free from substances that could impair the application of
coating
General data
Mounting type
Type AX
Functional earth ground
Weight
Housing material
MAC address table
MTTF
MTTF
MTTF
212 / 226
PHOENIX CONTACT
5.65
FL NAT 2008
EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B
EN 61000-6-2 EN 61000-4-5 (surge) Criterion B
EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A
FL NAT 2008
2702881
1
45 mm
130 mm
115 mm
IP20
III, VDE 0106
0 °C ... 60 °C
-40 °C ... 85 °C
10 % ... 95 % (non-condensing)
10 % ... 95 % (non-condensing)
86 kPa ... 108 kPa (1500 m above sea level)
86 kPa ... 108 kPa
Yes
DIN rail
Book type
The functional ground of the module is achieved when the
module is snapped onto the DIN rail.
220 g
Polycarbonate fiber reinforced
8k
507.8 Years (SN 29500 standard, temperature 25 °C,
operating cycle 21 % (5 days a week, 8 hours a day))
246.55 Years (SN 29500 standard, temperature 40 °C,
operating cycle 34.25 % (5 days a week, 12 hours a day))
56.66 Years (SN 29500 standard, temperature 55 °C,
operating cycle 100 % (7 days a week, 24 hours a day))
108997_en_04