Setting A Failsafe Output Value For Restart After A Power Loss - Honeywell UDC2800 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Motor Position Display
Table 5-18: Procedure for Displaying 3Pstep Motor Position
Step
Operation
1
Access the
Displays
Setting a Failsafe Output Value for Restart After
a Power Loss
Introduction
If the power to the controller fails and power is reapplied, the
controller goes through the power up tests, then goes to a user
configured FAILSAFE OUTPUT VALUE.
Set a Failsafe Value
Table 5-19: Procedure for Setting a Failsafe Value
Step
Operation
1
Select Control
Set-up Group
2
Select Failsafe
Function Prompt
3
Select a value
Chapter 5 - Monitoring and Operating the Controller
Press
Result
Lower
You will see OUT (The estimated motor position in
Display
%) in the main screen.
Press
Setup key or Increment
key or Decrement key
Function key
Increment key or
Decrement key
Function key
Increment key or
Decrement key
Result
Until you see Control set up
group.
Enter in the first function
prompt of Control set up group.
Until you see Failsafe Value
Enter in the value of Failsafe
Value.
To select a failsafe output value,
ranging from 0 to 100.
Except Three Position Step, for
Three Position Step:
0 Percent = motor goes to
210