Tune For Duplex (Heat/Cool); Using Automatic Tune At Start-Up For Duplex (Heat/Cool) - Honeywell UDC2800 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Tune for Duplex (Heat/Cool)

Accutune for applications using Duplex (Heat/Cool) control.
The controller must be configured to have two local setpoints unless
Blended Tuning is desired (see below). See Control Set Up Group for
more information. During tuning, the Accutune III process assumes
that Local Setpoint 1 will cause a Heating demand (output above
50%), and the tuning parameters calculated for that setpoint are
automatically entered as PID SET 1. Likewise, Accutune III assumes
that Local Setpoint 2 will cause a Cooling demand (output less than
50%), and the tuning parameters calculated for that setpoint are
automatically entered as PID SET 2.
Configuration Check for Duplex
See Accutune Set Up Group for more information.
Make sure:
n
n
Using AUTOMATIC TUNE at start-up for Duplex
(Heat/Cool)
Used when DUPLEX has been configured for AUTOMATIC.  This is
the preferred selection for most Heat/Cool applications when tuning
a new chamber.  This selection will sequentially perform both Heat
and Cool tuning without further operator intervention.
Table 5-8: Procedure for Using AUTOMATIC TUNE at Start-up for Duplex Control
Step
Operation
1
Configure
LSP1
2
Adjust LSP1
value
3
Configure
LSP2
Accutune is selected as Tune.
Duplex has been configured to Manual, Automatic or Disabled.
Press
Result
Lower
Until
Display key
display.
Increment
Until LSP1 is a value within the Heat Zone (output
key or
above 50%).
Decrement
key
Lower
Until
Display key
display.
Chapter 5 - Monitoring and Operating the Controller
(Local Setpoint 1) shows in the lower
SP
(Local Setpoint 2) shows in the lower
2SP