Honeywell UDC2800 Product Manual page 134

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Function
Selections or Range
Prompt
of Setting
Enable
Disable
Rate Up %
0 to 9999 % per
Min
minute
Rate Down
0 to 9999 % per
% Min
minute
Output High
Limit
0 % to 100 %
–5 % to 105 %
Output Low
Limit
0 % to 100 %
–5 % to 105 %
Integral High
Within the range of
Limit
the output limits
(Note 5)
Integral Low
Within the range of
Limit
the output limits
(Note 5)
Dropoff
–5 to 105 % of
output
(Note 5)
Parameter Definition
Allows output rate.
Disables output rate.
Output Rate Up Value
rate at which the output can change upward.
Enter a value in percent per minute. Appears
only if OUT RATE is enabled. "0" means no
output rate applied.
Output Rate Down Value
the rate at which the output can change
downward. Enter a value in percent per
minute. Appears only if OUT RATE is enabled.
"0" means no output rate.
- This is the highest value of
High Output Limit
output beyond which you do not want the
controller automatic output to exceed.
For relay output types.
For current output types.
- This is the lowest value of
Low Output Limit
output below which you do not want the
controller automatic output to exceed.
For relay output types.
For current output types.
- This is the highest value of
High Reset Limit
output beyond which you do not want reset
action to occur
- This is the lowest value of
Low Reset Limit
output beyond which you do not want reset
action to occur.
Controller Dropoff Value
which the controller output will drop off to the
low output limit value set in prompt Output
Low Limit.
Chapter 4 - Configuration
- This selection limits the
- This selection limits
- Output value below
134