Chapter 3 - Installation
Specifications
Operation
Dimensions
Mounting
Wiring
Connections
Power
Consumption
Power Inrush
Current
Weight
Isolation
(Functional)
Surge Withstand
Capability (SWC)
37
Automatic with Local Setpoint
Automatic with Remote Setpoint
See Overall Dimensions for more information.
Panel-mounted, 4.5-inch (114 mm) depth
Screw terminals on the rear of the case.
See Wiring Diagrams for more information.
16 VA maximum (100 to 240 Vac)
12 VA maximum (24 Vac/dc)
1.84 A maximum for 5.25 ms (under operating conditions),
reducing to a maximum of 200 mA (100 to 240 Vac operation) or
312 mA (24 Vac/dc operation) after 8.42 ms.
CAUTION: When applying power to more than one
instrument, make sure that sufficient power is supplied.
Otherwise, the instruments may not start up normally due to
voltage drop from the inrush current.
3 lbs. (1.3 kg)
AC Power(100~240VAC)
and outputs to withstand a HIPOT potential of 3000 Vac for 60
seconds, from earth ground to withstand a HIPOT potential of
1500 Vac for 60 seconds per EN61010-1.
DC Power(24VDC/AC)
outputs and earth ground to withstand a HIPOT potential of 840
Vac for 60 seconds per EN61010-1.
Analog Inputs and Outputs
isolated from all other circuits to withstand a HIPOT potential of
1500 Vac for 60 seconds.
: With a working voltage of 125/250 Vac, these are
Relay Contacts
electrically isolated from all other circuits to withstand a HIPOT
potential of 3000 Vac for 60 seconds per EN61010-1.
Immunity: ANSI/IEEE C37.90.1, Surge Withstand Capability (SWC)
(Formerly IEEE 472). Mains power input and relay contact outpus:
2.5 kV, Common Mode and Differential Mode. All other circuits: 1.0
: Electrically isolated from all other inputs
: Electrically isolated from all other inputs and
,
Digital Inputs and Outputs