SPYDER MODEL 5 ENGINEERING TOOL – USER GUIDE
3. Navigate to the folder where the firmware file is located, then select the firmware file (IRMN4-IMG_Vxxxx.bin), and
then click the Open button.
RESULT: The firmware download process is started as indicated on the top in the Firmware Download progress bar.
When the firmware download is finished successfully, it is indicated by the ´Success` message.

ALARMING

Alarm configuration and details on how to use NC objects in BACnet points and generate alarms and get it in Niagara.
To use the alarming function, please refer to the N4.x BACNET UTILITIES DRIVER User Guide, form no. EN2Z-
1020GE51.

MISCELLANEOUS

Value Updates after Device Power Failure

If a device had a power failure and the device is restarting, it will take 3 - 5 minutes until the values will be updated in the
wire sheet. To accelerate the value update on the wire sheet, please manually refresh the wire sheet by navigating to
another page and returning to the wire sheet.

Hiding Slots

Procedure
1. Right-click the function block icon, of which you want to hide slots.
2. In the context menu, click Pin Slots.
31-00282ES-01
108