Honeywell UDC2800 Product Manual page 341

Universal digital controller
Hide thumbs Also See for UDC2800:
Table of Contents

Advertisement

Chapter 11 - Modbus RTU Function Codes 20&21
Table 11-20: Set-up Group – Setpoint Program 5
Parameter Description
SP Program 5
Start Segment
End Segment
Ramp Unit
Recycles
Segment 1 Ramp
Segment 2 SP
Segment 2 Time
Segment 3 Ramp
Segment 4 SP
Segment 4 Time
Segment 5 Ramp
341
Register Address
Data
Type
Hex
Decimal
847
2119
INT
848
2120
INT
849
2121
INT
84A
2122
INT
84B
2123
INT
6F
111
FP
70
112
FP
71
113
FP
72
114
FP
73
115
FP
74
116
FP
75
117
FP
Data Range or
Access
Enumerated
Selection
0 = Disabled
R/W
1 = Enabled
Ramp segment
R/W
1 to 8
R/W
Soak segment
0 = Soak 8
1 = Soak 6
2 = Soak 4
3 = Soak 2
0 = Time Hrs:Mins
R/W
1 = Rate EU/Mins
2 = Rate EU/Hrs
0 to 100
R/W
99.59 (0-99 Hrs:0
R/W
-59 Min)  or
0 to 999
(Degrees/Minute)
Within Setpoint
R/W
Limits
99.59 (0-99 Hrs:0
R/W
-59 Min)
99.59 (0-99 Hrs:0
R/W
-59 Min)  or
0 to 999
(Degrees/Minute)
Within Setpoint
R/W
Limits
99.59 (0-99 Hrs:0
R/W
-59 Min)
99.59 (0-99 Hrs:0
R/W
-59 Min)  or

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents