9 .1 6 Descript ion Of Pa ra m et ers: Fa ct ory Set t ings
D H W Fa st M odu la t ion
0 0 = St andard Modulat ion - on DHW call for heat 10 seconds st abilizat ion t im e before
P0 1
m odulat ion
0 1 = Fast Modulat ion- on DHW call for heat 5 seconds st abilizat ion t im e before m odulat ion
Gas used
P0 2
0 0 = Gas A (Natural Gas)
0 1 = Gas E (LPG Gas)
Hydraulic system
0 0 = instantaneous appliance
0 3 = instantaneous appliance with pre-heat function
0 4 = heating only appliance with DHW therm ostat
P0 3
0 5 = appliance with external storage indirect tank
0 8 = heating only appliance
1 3 = instantaneous appliance with pre-heat function for solar application
P0 9
Hydraulic Com ponent Setting (1 = Brass)
Heating set-point setting OT / RT (Open Therm / Room Therm ostat 120V~ )
0 0 = with Rem ote Control (RC) connected, tem perature request is RC set-point
P1 0
0 1 = Tem perature Request is highest set point between RC and PCB
0 2 = Tem perature request is RU setpoint. The RT enable the gas boiler operates
P1 3
Max. heating output ( 0 - 1 0 0 % )
P1 4
DHW m ax. output ( 0 - 1 0 0 % )
P1 5
Min. heating output ( 0 - 1 0 0 % )
Maxim um CH set-point (° C)
0 0 = 176° F (80° C)
P1 6
0 1 = 113° F (45° C)
Selectable Range 2 0 - 8 0 = ( 2 0 ° C to 8 0 ° C) 6 8 ° F to 1 7 6 ° F
P1 7
Pum p overrun tim e in heating m ode ( 0 1 - 2 4 0 m inutes)
P1 8
Burner on delay with new call for heat ( 0 - 1 0 m inutes)
P2 0
Pum p overrun tim e in DHW m ode ( seconds)
Anti-legionellosis function
P2 1
0 0 = Disabled -
0 1 = Enabled
Manufacturer inform ation
P2 2
(set "2 2 " to access param eters 4 2 and above)
P2 3
Maxim um DHW set-point tem perature 1 1 3 ° - 1 4 0 ° F ( 4 5 ° - 6 0 ° C) , Default 4 9 = 1 2 0 ° F
P2 4
Manufacturer inform ation
P2 6 ..P3 1
Manufacturer inform ation
P3 2 ..P4 1
Diagnostics
Tem perature unit setting
0 0 = ° C
P4 4
0 1 = ° F
OT/ RT (Open Therm / Room Therm ostat) selection.
P6 7
2 = OT (open therm STD)
Pa ra m et ers cont inued on nex t pa ge
9 - START U P PROCED U RE
5 7
FACTORY SETTI N GS
7 5
1 0 0 ,1 2 5 ,1 6 5 1 1 5 ,1 5 0 ,2 0 5
01
00
08
Default 01
00
73
100
100
00
00
03
03
30
00
00
49
35
--
--
01
02
240013687 REV A [ 09/ 01/ 2022]