ADP1046A 100Watt
Evaluation board
B.
Internal short circuit action on OrFET: Figure 52 and Figure 53 shows the OrFET disabled during an internal short
circuit and its corresponding flag. An internal short of the synchronous rectifiers can be simulated in the PWM settings
or by physically shorting the drain pin of Q2 and Q3. The CS1 fast OCP or the UVP flags can be set to disable the
OrFET.
Figure 52 - Synchronous rectifiers shorted, 48VDC, 8A load
Upper trace: OrFET gate voltage, 10V/div, 5us/div
Lower trace: Primary current, 5A/div, 5us/div
Figure 51 - OrFET disabled when VS3 is greater than OVP limit
Green trace: Output voltage
Red trace: OrFET Gate signal
Rev. 1.3 | Page 32 of 55
Figure 53 - Corresponding 'Flags and Readings" window. UVP was the first
flag that tripped
PRD1386