Fig.4
Control box
1
2
3
4
2.3
Introduction to the e-Smart controls platform
Fig.5
Generic example
SCB
GTW
MK
Tab.2
Components in the example
Item
Description
CU
Control Unit: Control unit
CB
Connection Board: Connection PCB
SCB
Smart Control Board: Expansion PCB
GTW
Gateway: Conversion PCB
MK
Control panel: Control panel and display
RU
Room Unit: Room unit (for example, a thermo
stat)
L-Bus
Local Bus: Connection between devices
S-Bus
System Bus: Connection between appliances
R-Bus
Room unit Bus: Connection to a room unit
A
Device
B
Appliance
C
System
7837115 - v.01 - 10012023
1 Display cover
2 Power button
3 Control panel
4 Service connector
5 Control box front part - for expansion PCBs and gateways
6 Control box rear part - for the control unit and expansion PCBs
5
6
AD-3002432-01
The Gas 210 Ace boiler is equipped with the e-Smart controls platform.
This is a modular system, and offers compatibility and connectivity
between all products that make use of the same platform.
R-Bus
CU
CB
L-Bus
S-Bus
GTW
RU
Function
The control unit handles all basic functionality of the appli
ance.
The connection PCB provides easy access to all connectors
of the control unit.
An expansion PCB provides extra functionality, like an internal
calorifier or multiple zones.
A gateway can be fitted to an appliance or system, to provide
one of the following:
Extra (wireless) connectivity
Service connections
Communication with other platforms
The control panel is the user interface to the appliance.
A room unit measures the temperature in a reference room.
The local bus provides communication between devices.
The system bus provides communication between appliances.
The room unit bus provides communication to a room unit.
A device is a PCB, control panel or a room unit.
An appliance is a set of devices connected via the same L-
Bus
A system is a set of appliances connected via the same S-Bus
2 Description of the product
C
B
A
AD-3001366-02
7