7 Maintenance
Fig.60
Cleaning the heat exchanger
7
6
7.4.5
Cleaning the condensate collector
Fig.61
Cleaning the condensate collector
1
2
7.4.6
Cleaning the trap
Fig.62
Cleaning the trap
2
Fig.63
Filling the trap
4
5
54
AD-3002499-01
3
AD-3002487-01
AD-3002488-01
6
AD-3002489-01
6. Fit the inspection cover and the gasket with a new silicon cord.
7. Use clean water to thoroughly rinse the heat exchanger from the
burner area.
1. Remove the sealing cap from the condensate collector.
2. Thoroughly rinse the condensate collector for at least 5 minutes, with
the largest possible water flow.
3. Refit the sealing cap on the condensate collector.
1. Remove the trap.
2. Clean the trap with water.
3. Put the trap back in place.
4. Remove the sealing cap from the condensate collector.
5. Fill the trap with water via the condensate collector.
Danger
The trap must always be sufficiently filled with water. This
prevents flue gases from entering the room.
6. Refit the sealing cap on the condensate collector.