Alarm Code Output Selection (Pr.76) - Mitsubishi Electric FR-F740-00023-EC Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-F740-00023-EC:
Table of Contents

Advertisement

Operation setting at alarm occurrence

3.12.2 Alarm code output selection (Pr.76)

At alarm occurrence, its description can be output as a 4-bit digital signal from the open collector output
Pr. 75
terminals.The alarm code can be read by a programmable controller, etc., and its corrective action can be shown
page 142
on a display, etc.
Pr. 77
page 145
Parameter
Number
76
Alarm code output selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 146)
(1) Alarm code output function
⋅ By setting Pr. 76 to "1" or "2", the alarm code can be output to the output terminals.
⋅ When the setting is "2", an alarm code is output at only alarm occurrence, and during normal operation, the terminals
output the signals assigned to Pr. 190 to Pr. 196 (output terminal function selection).
⋅ The following table indicates alarm codes to be output. (0: output transistor off, 1: output transistor on)
Operation Panel
Other than the above
* When Pr. 76 = "2", the output terminals output the signals assigned to Pr. 190 to Pr. 196 .
CAUTION
⋅ Refer to page 189 for details of alarm code.
⋅ When a value other than "0" is set in Pr.76
When an alarm occurs, the output terminals SU, IPF, OL, FU output the signal in the above table, independently of the Pr. 190 to
Pr. 196 (output terminal function selection) settings. Please be careful when inverter control setting has been made with the outut
signals of Pr. 190 to Pr. 196.
♦ Parameters referred to ♦
Pr. 190 to Pr. 196 (output terminal function selection)
122
Name
Indication
SU
(FR-DU07)
Normal *
0
E.OC1
0
E.OC2
0
E.OC3
0
E.OV1 to E.OV3
0
E.THM
0
E.THT
0
E.IPF
0
E.UVT
1
E.FIN
1
E. BE
1
E. GF
1
E.OHT
1
E.OLT
1
E.OPT
1
E.OP1
1
1
Initial Value
Setting Range
0
1
0
2
Output of Output Terminals
IPF
OL
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
1
1
Refer to page 96
Description
Without alarm code output
With alarm code output
(Refer to the following table)
Alarm code output at alarm occurrence
only (Refer to the following table)
Alarm Code
FU
0
0
1
1
0
2
1
3
0
4
1
5
0
6
1
7
0
8
1
9
0
A
1
B
0
C
1
D
0
E
0
E
1
F

Advertisement

Table of Contents
loading

Table of Contents