Parameter Verification - Mitsubishi Electric FR-F740-00023-EC Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-F740-00023-EC:
Table of Contents

Advertisement

appears...Why?
appears...Why?
and
Appears when parameters are copied between the inverter of 01160 or less and 01800 or more.
1. Set "0" in Pr. 160 User group read selection.
2. Set the following setting (initial value) in Pr. 989 Parameter copy alarm release.
Pr. 989 Setting
3. Reset Pr. 9, Pr. 30, Pr. 51, Pr. 52, Pr. 54, Pr. 56, Pr. 57, Pr. 70, Pr. 72, Pr. 80, Pr. 90, Pr. 158, Pr. 190 to Pr. 196, Pr. 893.

3.24.2 Parameter verification

Whether same parameter values are set in other inverters or not can be checked.
Operation
1.
Replace the operation panel on the
inverter to be verified.
• Replace it during a stop.
2.
Screen at powering on
The monitor display appears.
3.
Press
to choose the parameter
setting mode.
4.
Turn
until
appears.
5.
Press
to read the currently set
value.
"
"(initial value) appears.
6.
Turn
to change it to the set value
" "(parameter copy verification mode).
7.
Press
to read the parameter setting
of the verified inverter to the operation panel.
• If different parameters exist, different
parameter numbers and
• Hold down
8.
It there is no difference,
flicker to complete verification.
REMARKS
When the copy destination inverter is not the FR-F700 series, "model error (
flickers ... Why?
Set frequencies, etc. may be different. Check set frequencies.
Parameter read error. Perform operation from step 3 again.
Parameter write error. Perform operation from step 8 again.
flicker alternately
01160 or less
10
(parameter copy)
flicker.
to verify.
and
Parameter copy and parameter verification
01800 or more
Display
The parameter
number read
previously appears.
The frequency flickers
for about 30s
Flicker ··· Parameter verification complete!!
)" is displayed.
100
Flickering
3
229