Function assignment of external
terminal and control
3.9.5

Output terminal function selection (Pr. 190 to Pr. 196)

You can change the functions of the open collector output terminal and relay output terminal.
Pr.189
page 90
Parameter
Pr.232
page 72
Number
RUN terminal
190
function selection
SU terminal function
191
selection
IPF terminal function
192
selection
OL terminal function
193
selection
FU terminal function
194
selection
ABC1 terminal
195
function selection
ABC2 terminal
196
function selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 146)
(1) Output signal list
⋅ You can set the functions of the output terminals.
⋅ Refer to the following table and set the parameters: (0 to 99: Positive logic, 100 to 199: Negative logic)
Setting
Positive
Negative
Logic
Logic
0
100
1
101
2
102
3
103
4
104
5
105
7
107
8
108
10
110
11
111
12
112
13
113
96
Name
Open
collector
output
terminal
Relay
output
terminal
Signal
Function
Name
RUN
Inverter running
SU
Up to frequency
*1, 2
Instantaneous power
IPF
failure/undervoltage
OL
Overload alarm
Output frequency
FU
detection
*2
Second output
FU2
frequency detection
Regenerative brake
RBP
prealarm
Electronic thermal
THP
relay function
prealarm
PU
PU operation mode
Inverter operation
RY
ready
Output current
Y12
detection
Zero current
Y13
detection
Initial
Initial Signal
Value
0
RUN (inverter running)
1
SU (up to frequency)
IPF (instantaneous power
2
failure, undervoltage)
3
OL (overload alarm)
FU (output frequency
4
detection)
99
ALM (alarm output)
9999
No function
Operation
Output during operation when the inverter
output frequency rises to or above Pr. 13
Starting frequency.
Output when the output frequency is
reached to the set frequency.
Output at occurrence of an instantaneous
power failure or when undervoltage
protection is activated.
Output while stall prevention function is
activated.
Output when the output frequency reaches
the frequency setting in Pr. 42 (Pr. 43 for
reverse rotation).
Output when the output frequency reaches
the frequency setting in Pr. 50.
*2
Output when 85% of the regenerative brake
duty set in Pr. 70 is reached.
Setting can be made for the 01800 or more.
Output when the electronic thermal relay
function cumulative value reaches 85%.
(Electronic thermal relay function protection
(E.THT/E.THM) actirates, when the value
reached 100%.)
Output when the PU operation mode is selected.
Output when the inverter can be started by
switching the start signal on or while it is running.
Output when the output current is higher
than the Pr. 150 setting for longer than the
time set in Pr. 151.
Output when the output power is lower than
the Pr. 152 setting for longer than the time
set in Pr. 153.
Setting Range
0 to 5, 7, 8, 10 to 19, 25, 26,
45 to 47, 64, 70 to 78, 90 to 96, 98,
99, 100 to 105, 107, 108, 110 to
116, 125, 126, 145 to 147, 164,
170, 190 to 196, 198, 199, 9999
0 to 5, 7, 8, 10 to 19, 25, 26, 45 to
47, 64, 70 to 78, 90, 91, 94 to 96,
98, 99, 100 to 105, 107, 108, 110
to 116, 125, 126, 145 to 147, 164,
170, 190, 191, 194 to 196, 198,
199, 9999
Related
Refer
Parameters
to Page
Pr. 41
Pr. 57
Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
Pr. 149, Pr. 154
Pr. 42, Pr. 43
Pr. 50
Pr. 70
Pr. 9
Pr. 79
Pr. 150, Pr. 151
Pr. 152, Pr. 153
98
100
114
60
100
100
88
84
148
98
101
101