1.1.1

Peripheral devices

Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be selected according to the
capacity. Refer to the following list and prepare appropriate peripheral devices:
400V class
Motor
Output
Applicable Inverter Type
(kW)
*1
0.75
FR-F740-00023-EC
1.5
FR-F740-00038-EC
2.2
FR-F740-00052-EC
3.7
FR-F740-00083-EC
5.5
FR-F740-00126-EC
7.5
FR-F740-00170-EC
11
FR-F740-00250-EC
15
FR-F740-00310-EC
18.5
FR-F740-00380-EC
22
FR-F740-00470-EC
30
FR-F740-00620-EC
37
FR-F740-00770-EC
45
FR-F740-00930-EC
55
FR-F740-01160-EC
75
FR-F740-01800-EC
90
FR-F740-01800-EC
110
FR-F740-02160-EC
132
FR-F740-02600-EC
160
FR-F740-03250-EC
185
FR-F740-03610-EC
220
FR-F740-04320-EC
250
FR-F740-04810-EC
280
FR-F740-05470-EC
315
FR-F740-06100-EC
355
FR-F740-06830-EC
400
FR-F740-07700-EC
450
FR-F740-08660-EC
500
FR-F740-09620-EC
560
FR-F740-10940-EC
630
FR-F740-12120-EC
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 400VAC 50Hz.
*2
Select the MCCB according to the inverter power supply capacity.
Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to the Instruction Manual (basics).)
*3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the
MC with class AC-3 rated current for the motor rated current.
*4
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc.
Identify the cause of the trip, then remove the cause and power on the breaker.
Breaker Selection
Reactor connection
without
with
30AF 5A
30AF 5A
30AF 10A
30AF 10A
30AF 10A
30AF 10A
30AF 20A
30AF 15A
30AF 30A
30AF 20A
30AF 30A
30AF 30A
50AF 50A
50AF 40A
100AF 60A
50AF 50A
100AF 75A
100AF 60A
100AF 100A
100AF 75A
225AF 125A
100AF 100A
225AF 150A
225AF 125A
225AF 175A
225AF 150A
225AF 200A
225AF 175A
225AF 225A
225AF 225A
225AF 225A
400AF 400A
400AF 400A
400AF 400A
600AF 500A
600AF 600A
600AF 600A
800AF 700A
800AF 800A
1000AF 900A
1000AF 1000A 1000AF 1000A
1200AF 1200A 1200AF 1200A
1600AF 1500A 1600AF 1600A
2000AF 2000A 2000AF 2000A
Inverter and peripheral devices
Input Side Magnetic
*2,4
Contactor
Reactor connection
with commercial
power-supply
without
operation
30AF 5A
S-N10
30AF 10A
S-N10
30AF 15A
S-N10
30AF 20A
S-N10
30AF 30A
S-N20
30AF 30A
S-N20
50AF 50A
S-N20
100AF 60A
S-N25
100AF 75A
S-N25
100AF 100A
S-N35
225AF 125A
S-N50
225AF 150A
S-N65
225AF 175A
S-N80
225AF 200A
S-N80
225AF 225A
400AF 300A
400AF 350A
400AF 400A
600AF 500A
600AF 500A
600AF 600A
600AF 600A
800AF 800A
800AF 800A
800AF 800A
1000AF 1000A
MCCB
MCCB
*3
with
S-N10
S-N10
S-N10
S-N10
S-N11, N12
S-N20
S-N20
S-N20
S-N25
S-N25
S-N50
S-N50
S-N65
S-N80
S-N95
S-N150
S-N180
S-N220
S-N300
S-N300
S-N400
S-N600
S-N600
S-N600
S-N600
1
S-N800
1000A
Rated product
1000A
Rated product
1200A
Rated product
1400A
Rated product
INV
IM
INV
IM
3