4.2 Causes and corrective actions

(1) Error Message
A message regarding operational troubles is displayed. Output is not shut off.
Operation Panel
Indication
Name
Operation panel lock
Description
Operation lock mode is set. Operation other than
Check point
Corrective action
Press
Operation Panel
Indication
Name
Write disable error
1. You attempted to make parameter setting when Pr. 77 Parameter write selection has been set to
Description
2. Frequency jump setting range overlapped.
3. Adjustable 5 points V/F settings overlapped
4. The PU and inverter cannot make normal communication
1. Check the setting of Pr. 77 Parameter write selection (Refer to
2. Check the settings of Pr. 31 to 36 (frequency jump). (Refer to
Check point
3. Check the settings of Pr. 100 to Pr. 109 (Adjustable 5 points V/F). (Refer to
4. Check the connection of the PU and inverter.
Operation Panel
Indication
Name
Write error during operation
When parameter write was performed during operation with a value other than "2" (writing is enabled
Description
independently of operation status in any operation mode) is set in Pr. 77 and the STF (STR) is on.
1. Check the Pr. 77 setting. (Refer to
Check point
2. Check that the inverter is not operating.
1. Set "2" in Pr. 77.
Corrective action
2. After stopping operation, make parameter setting.
Operation Panel
Indication
Name
Calibration error
Description
Analog input bias and gain calibration values are too close.
Check point
Check the settings of C3, C4, C6 and C7 (calibration functions). (Refer to
Operation Panel
Indication
Name
Mode designation error
Description
You attempted to make parameter setting in the NET operation mode when Pr. 77 is not "2".
1. Check that operation mode is "PU operation mode".
Check point
2. Check the Pr. 77 setting. (Refer to
1. After setting the operation mode to the "PU operation mode", make parameter setting. (Refer to page
Corrective action
2. After setting "2" in Pr. 77, make parameter setting.
Operation Panel
Indication
Name
Parameter read error
Description
An error occurred in the EEPROM on the operation panel side during parameter copy reading.
Check point
· Make parameter copy again. (Refer to page 228.)
Corrective action
· Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
HOLD
for 2s to release lock.
Er1
disable parameter write.
Er2
Er3
Er4
145.)
rE1

Causes and corrective actions

is made invalid. (Refer to page 225.)
-- -- -- - -- -- - --
page 145.)
page 67.)
page 145.)
page 145.)
-- -- -- - -- -- - --
page 71.)
page 135.)
235