Motor brake and stop operation
3.8.2

Selection of a regenerative brake (Pr. 30, Pr. 70)

Use the "high power factor converter (FR-HC, MT-HC) to reduce harmonics, improve the power factor, or
Pr. 29
Pr.29
continuously use the regenerative mode.
page 82
page 82
Pr.31
Pr.31
page 67
page 67
Parameter
Pr.69
Number
page 120
Pr.71
page 85
30
Regenerative function selection
70
Special regenerative brake duty
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 146)
(1) When the brake unit (BU, FR-BU) is used
⋅ Set "0" (initial value) in Pr. 30. The Pr. 70 setting is made invalid.
(2) When using a brake unit (MT-BU5) and power regeneration converter (MT-RC) (01800 or
more)
⋅ Set "1" in Pr. 30.
⋅ Set "10%" In Pr. 70 when using a brake unit (MT-BU5).
⋅ Set "0%" in Pr. 70 when using a power regeneration converter (MT-RC).
(3) When using the high power factor converter (FR-HC, MT-HC) or power regeneration
common converter (FR-CV)
⋅ Set "2" in Pr. 30. The Pr. 70 setting is made invalid.
⋅ Use any of Pr. 178 to Pr. 189 (Input terminal function assignment) to assign the following signals to the contact input
terminals.
(a) X10 signal: FR-HC, MT-HC connection, FR-CV connection (inverter operation enable signal)
To make protective coordination with the FR-HC, MT-HC or FR-CV, use the inverter operation enable signal
to shut off the inverter output. Input the RDY signal of the FR-HC, MT-HC (RDYB signal of the FR-CV).
(b) X11 signal: FR-HC, MT-HC connection (instantaneous power failure detection signal)
When the setting has been made to hold the mode at occurrence of an instantaneous power failure for RS-
485 communication operation, use this signal to hold the mode. Input the Y1 or Y2 signal (instantaneous
power failure detection signal) of the FR-HC, MT-HC.
⋅ For the terminal used for X10 or X11 signal input, assign its function by setting "10" (X10) or "11" (X11) to any of Pr.
178 to Pr. 189.
REMARKS
⋅ The MRS signal can also be used instead of the X10 signal. (Refer to page 90.)
⋅ Refer to pages 20 to 24 for connection of the brake unit, high power factor converter (FR-HC, MT-HC) and power regeneration
common converter (FR-CV).
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
make setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 178 to Pr.189 (input terminal function selection)
88
Name
Initial Value
Refer to page 90
Setting Range
0
1
0
2
0%
0 to 10%
Description
Without regenerative function,
brake unit (FR-BU, BU type)
Brake unit (MT-BU5), power
regeneration converter (MT-RC)
(Setting can be made only for the
01800 or more)
High power factor converter (FR-
HC, MT-HC), power regeneration
common converter (FR-CV)
Set the %ED of the brake transistor
operation when using a brake unit
(MT-BU5).
(Setting can be made only for the
01800 or more