Motor brake and stop operation

3.8 Motor brake and stop operation

Purpose
Motor braking torque adjustment
Improve the motor braking torque
with an option
Coast the motor to a stop
3.8.1

DC injection brake (Pr. 10 to Pr. 12)

The DC injection brake can be operated at a motor stop to adjust the stop timing and braking torque.
Pr. 9
page 83
Parameter
Pr. 13
Number
page 81
DC injection brake
10
operation frequency
DC injection brake
11
operation time
DC injection brake
12
operation voltage
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 146)
When Pr. 11="0.1 to 10s"
DC injection
Pr.12
Operation
brake
voltage
voltage
When Pr. 11="8888"
DC injection
Pr.12
Operation
brake
voltage
voltage
X13 signal
86
DC injection brake
Selection of a regenerative brake
Selection of motor stopping method
Name
00170 or less
00250 to 01160 or
01800 or more
(1) Operation frequency setting (Pr. 10)
⋅ When the frequency at which the DC injection brake operates is set in
Pr. 10, the DC injection brake is operated when this frequency is reached
during deceleration.
⋅ At the Pr. 10 setting of "9999", the DC injection brake is operated when
deceleration is made to the frequency set in Pr. 13 Starting frequency.
(2) Operation time setting (Pr. 11)
Time
⋅ Use Pr. 11 to set the duration period the DC injection brake is applied.
⋅ When Pr. 11 = "0s", the DC injection brake is not operated. (At a stop, the
motor coasts.)
Time
⋅ When Pr. 11="8888", the DC injection brake is applied while X13 signal
Pr.11 Operation time
is on.
⋅ For the terminal used for X13 signal input, set "13" in any of Pr. 178 to Pr.
189 to assign the function. (Refer to page 90.)
⋅ When the motor does not stop due to large load moment (J), increasing
the setting produces an effect.
Time
Time
ON OFF
Parameter that must be set
Initial Value
Setting Range
0 to 120Hz
3Hz
0.5s
0.1 to 10s
4%
2%
0 to 30%
more
1%
Pr. 10 to Pr. 12
Pr. 30
Pr. 250
Description
Set the operation frequency of the
DC injection brake.
9999
Operated at Pr. 13 or less.
0
DC injection brake disabled
Set the operation time of the DC
injection brake.
8888
Operate when X13 signal is on
Set the DC injection brake voltage
(torque). When "0" is set, DC injection
brake is disabled.
Refer to Page
86
88
89