Mitsubishi Electric FR-F740-00023-EC Instruction Manual page 267

Frequency inverter
Hide thumbs Also See for FR-F740-00023-EC:
Table of Contents

Advertisement

Common specifications
Operating
status
PU
(FR-DU07/
FR-PU04)
Alarm
definition
Interactive
guidance
Protective/warning function
LD
Ambient
SLD
temperature
(initial setting)
Ambient humidity
Storage temperature
*3
Atmosphere
Altitude, vibration
*1
Can be displayed only on the operation panel (FR-DU07).
*2
Can be displayed only on the parameter unit (FR-PU04).
*3
Temperature applicable for a short period in transit, etc.
*4
Only the 01800 or more functions.
2
*5
2.9m/s
or less for the 04320 or more.
256
Output frequency, motor current (steady or peak value), output voltage, alarm indication,
frequency setting, running speed, converter output voltage (steady or peak value), electronic
thermal relay function load factor, input power, output power, load meter, cumulative energization
time, actual operation time, motor load factor, cumulative power, power saving effect, cumulative
saving power, regenerative brake duty
inverter I/O terminal monitor, input terminal option monitor
option fitting status monitor
, terminal assignment status
*2
Alarm definition is displayed during the protective function is activated, output voltage/
current/frequency/cumulative energization time and eight past alarm definition is stored.
Operation guide/trouble shooting with a help function
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during
deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage
during deceleration, inverter protection thermal operation, motor protection thermal operation,
heatsink overheat, instantaneous power failure occurrence, undervoltage, input phase failure,
motor overload, output side earth fault overcurrent, output phase failure, external thermal relay
operation, PTC thermistor operation, option alarm, parameter error, PU disconnection, retry
count excess, CPU alarm, operation panel power supply short circuit, 24VDC power output
short circuit, output current detection value excess, inrush current limit circuit alarm,
communication alarm (inverter), analog input alarm, internal circuit error (15V power supply),
fan fault, overcurrent stall prevention, overvoltage stall prevention, electronic thermal relay
function prealarm, PU stop, maintenance timer alarm
parameter write error, copy operation error, operation panel lock, parameter copy
-10°C to +50°C (non-freezing)
-10°C to +40°C (non-freezing)
90%RH or less (non-condensing)
-20°C to +65°C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Maximum 1000m above sea level for standard operation. After that derate by 3% for every
extra 500m up to 2500m (92%) 5.9m/s
,PID set point, PID measured value, PID deviation value,
*4
, output terminal option monitor
*1
*2
*2
, brake transistor alarm detection
*1
2
or less
(conforming to JIS C 60068-2-6)
*5
,
*1
,
*4