Input Settings - Huawei UPS5000-E-30 kVA User Manual

Integrated ups
Table of Contents

Advertisement

UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS)
Item
BCB trips if
UPS stops
power supply

4.2.4.3 Input Settings

Figure 4-28 Input Settings
Item
D.G. mode
D.G. power
limiting (kVA)
D.G. charger
power ratio
(%)
Input cur.
limiting
Issue 02 (2022-12-30)
Description
Specifies whether the BCB
trips when the UPS stops
supplying power and the
output power is off.
Description
Set this parameter to Enable
when a DG connects to the
input power distribution
cabinet (PDC). The UPS
enters the DG mode when a
DG is detected over dry
contacts.
The two parameters enable
the UPS to control the valid
input current and input
current limit values,
preventing load impact and
facilitating cooperation
between the UPS and the
DG.
Specifies whether to enable
or disable input current
limiting for the UPS to
protect the generator.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
Enable
Disable,
Enable
Default Value
Value Range
Disable
Disable,
Enable
Depends on
0–5000
the actual
model.
100
0–100
Disable
Disable,
Enable
102