UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS)
Step 2 Clear the EPO alarm in the system.
Step 3 View active alarms and check that the EPO alarm is cleared. If the system bypass
input is normal, the UPS transfers to bypass mode.
Choose System Info and tap
and check whether the EPO alarm is cleared.
Step 4 Start the inverter.
----End
Issue 02 (2022-12-30)
Choose System Info, tap
In the displayed dialog box, tap Yes to clear the EPO alarm.
Figure 5-14 Alarms screen
Figure 5-15 Clearing faults
Copyright © Huawei Digital Power Technologies Co., Ltd.
to enter the Alarms screen, and tap Clear Fault.
to enter the Alarms screen. Tap Active Alarms
5 Operations