Huawei UPS5000-E-30 kVA User Manual page 116

Integrated ups
Table of Contents

Advertisement

UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS)
Item
Single battery
voltage(V)
Single battery
capacity(Ah)
Batteries in a
battery string
Number of
battery
strings
Installation
time
Maintenance
period(d)
Cell float
voltage(V/
cell)
Cell equalized
volt.(V/cell)
Dis. curr. 0.1C
EOD(V/cell)
Dis. curr. 0.3C
EOD(V/cell)
Dis. curr. 0.5C
EOD(V/cell)
Dis. curr. 1.0C
EOD(V/cell)
Shallow
discharge test
Issue 02 (2022-12-30)
Description
Specifies the voltage of each
battery that is connected in
series in a battery string.
Specifies the capacity of each
battery that is connected in
series in a battery string.
Specifies the number of
batteries in a battery string.
Specifies the number of
battery strings connected in
parallel.
A battery maintenance
reminder is displayed when
the maintenance time
(counted from the
installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
Specifies the battery float
charging voltage.
Specifies the battery
equalized charging voltage.
Specifies the EOD threshold
when the discharge current is
0.1C, 0.3C, 0.5C, or 1.0C
respectively.
When certain conditions are
met, the charger shuts down,
and batteries supply power
to loads. The system records
the battery discharge data as
a reference for battery
capacity and lifespan.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
12 V
2, 6, 12
Depends on
5–9999
the actual
model.
Depends on
The value
the model.
range depends
on the model.
1
1–6
-
-
0
0–365
2.25
2.23–2.30
2.35
2.30–2.40
1.80
1.80–1.90
1.80
1.80–1.90
1.75
1.75–1.85
1.60
1.60–1.75
Disable
Disable,
Enable
108