● The battery string voltage may cause serious injury. Observe safety precautions
● Ensure that cables are correctly connected between the battery strings and the
● When multiple battery strings need to be connected, only batteries of the same
Figure 3-27 Connecting battery cables
A neutral wire is routed from the middle of the positive and negative battery
strings.
Take a battery string consisting of 40 batteries for example. The battery neutral
wire is routed from the middle of positive and negative battery strings, each
consisting of 20 batteries.
Figure 3-28 Battery neutral wire
Issue 02 (2022-12-30)
D ANGER
when connecting cables.
battery circuit breaker, and between the circuit breaker and the UPS. Reverse
connections are prohibited.
or similar model recommended by the manufacturer can be used.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
71