UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS)
Item
System
overfrequency
threshold
(Hz)
Mains
overfrequency
alarm enable
Mains
underfrequen
cy alarm
enable
Branch
breaker open
alarm enable
Branch
exception
alarm enable
Voltage
harmonic
alarm
threshold (%)
Current
harmonic
alarm
threshold (%)
Issue 02 (2022-12-30)
Description
When the system frequency
is higher than the rated
frequency plus the value of
this parameter or is lower
than the rated frequency
minus the value of this
parameter, an alarm is
generated.
If this parameter is set to
Enable, an alarm is
generated when the alarm
condition is met.
If this parameter is set to
Enable, an alarm is
generated when the alarm
condition is met.
If this parameter is set to
Enable, the system generates
an alarm when the branch
circuit breaker opens. If this
parameter is set to Disable,
the system does not generate
the alarm under any
condition.
If this parameter is set to
Enable, the system generates
an alarm when the branch
circuit breaker is closed and
no load is connected. If this
parameter is set to Disable,
the system does not generate
the alarm under any
condition.
When Harmonic alarm
enable is set to Enable and
the mains voltage harmonic
value exceeds the alarm
threshold, the system
generates an alarm.
When Harmonic alarm
enable is set to Enable and
the mains current harmonic
value exceeds the alarm
threshold, the system
generates an alarm.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
1.5
1.0-10
Enable
Disable,
Enable
Enable
Disable,
Enable
Enable
Disable,
Enable,
Custom
Disable
Disable,
Enable,
Custom
30.0
5.0–30.0
30.0
5.0–30.0
115