Huawei UPS5000-E-30 kVA User Manual page 125

Integrated ups
Table of Contents

Advertisement

UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS)
Item
Undercurrent
threshold (%)
Three-phase
load
imbalance
(%)
Mains current
exceeding
lower
threshold
Mains current
exceeding
higher
threshold
Mains three-
phase current
imbalance
Issue 02 (2022-12-30)
Description
Branch and mains
undercurrent threshold.
When the mains or branch
current is higher than the
rated mains or branch
current multiplied by the
value of Undercurrent
threshold (%) and lower
than the rated current
multiplied by the value of
Overcurrent threshold (%),
the system generates an
alarm.
Mains three-phase current
imbalance alarm threshold.
When the difference between
the highest and lowest mains
three-phase currents is
higher than the alarm
threshold, the system
generates an alarm.
If this parameter is set to
Enable, the system generates
an alarm when the mains
current is below the lower
current threshold. If this
parameter is set to Disable,
the system does not generate
the alarm under any
condition.
If this parameter is set to
Enable, the system generates
an alarm when the mains
current exceeds the higher
current threshold. If this
parameter is set to Disable,
the system does not generate
the alarm under any
condition.
If this parameter is set to
Enable, the system generates
an alarm when the mains
three-phase current is
imbalanced. If this parameter
is set to Disable, the system
does not generate the alarm
under any condition.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
60.0
30.0–80.0
25.0
5.0–50.0
Enable
Disable,
Enable
Enable
Disable,
Enable
Enable
Disable,
Enable
117