Fig. 3 - Optional Single-Point Power Supply Connection With Individual; System Circuit Breakers - York YCAS0693 Wiring Diagram

Air-cooled liquid chillers, 3 /4 compressor/r22, style g, 50 hz
Table of Contents

Advertisement

OPTIONAL SINGLE POINT POWER SUPPLY
CONNECTION AND INDIVIDUAL SYSTEM CIRCUIT
BREAKERS
CB
1
CB
3
See notes below.
FIG. 3 – OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL
SYSTEM CIR CUIT BREAK ERS
NOTES:
1. – – – – – – – Dashed Line indicates Field Provided Wiring.
2. The above recommendations are based on the National Electrical Code and using copper conductors only.
Field wiring must also comply with local codes.
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL SYSTEM
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)
Chiller
Field Provided Power Supply
Volts MRA
1
Min NF
YCAS
(MCA)
Disc SW
2
0693
380
551
600
0773
380
625
800
0783
380
575
600
0873
380
685
800
0953
380
741
800
1063
380
826
1000
1093
380
872
1000
1163
380
914
1000
1263
380
989
1000
See page 6 for Electrical Data footnotes.
10
ELECTRICAL DATA (CONT'D)
CB
2
CB
4
CIRCUIT BREAKERS – 3 & 4 COMPRESSOR UNITS
in 'Option Panel'. Individual System Circuit Breakers in each Motor Control Center.)
Model
Over-Current Protection
13
Min.
3, 5
Max.
4, 6
600
600
700
700
600
600
700
700
800
800
800
800
1000
1000
1000
1000
1000
1000
Suitable for:
Y - ∆ Start and
Across-The-Line-Start
One fi eld provided power sup ply cir cuits to the unit with
in di vid u al branch cir cuit protection. Field Power Wiring
connections to fac to ry provided, Non-Fused Dis con nect
Switches (Opt), or Ter mi nal Blocks (Opt) in the Option
Box.
Suitable for:
Y - D Start and
Across the Line Start
TB
or
Field Supply
DS
LD05557
FIELD SUPPLIED WIRING
Factory Provided (Lugs) Wire Range
Terminal Block
(Lugs) Wire Range
(2)2/0-500
(2)2/0-500
(2)2/0-500
(3)1/0-300
(3)1/0-300
(3)2/0-500
(3)2/0-500
(3)2/0-500
(3)2/0-500
FORM 201.19-W4 (1104)
See Note 3 on
See Note 3
page 6.
7
NF Disc. Switch
(Lugs) Wire Range
(2)250-500
(3)2/0-400
(2)250-500
(3)2/0-400
(3)2/0-400
(4)4/0-500
(4)4/0-500
(4)4/0-500
(4)4/0-500
YORK INTERNATIONAL

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ycas0953Ycas1063Ycas1263

Table of Contents