Note: Table 3.5.2 shows the heating volumes at continuous rated output. In the heat
design of a cabinet housing servo units, 40 ~ 70 % of such values are normally
used, taking into consideration the number of simultaneously controlled axes and
load exerted on servo motors.
See the servo connection manuals for details.
Table 3.5.2
Type
SS101
SS161
AS14
AS28
AS42
AS56
AS85
AS86
AW28
AW42
AW56
AP28
RU09
RU10
RU12
– 41 –
Heating volume
100 W
180 W
140 W
270 W
420 W
580 W
890 W
810 W
290 W
420 W
550 W
320 W
See the servo
connection manual.