When the servo contactor external control input (P24V - PONI)on the servo
power supply unit is opened or external power supply for the servo contactor
(MC) is opened, the servo contactor (MC) is turned off and the servo axes are
stopped by dynamic brake.
6)
Usually, the servo contactor (MC) should be turned off after the main control
unit decelerates and stops axes. Thus use an OFF DELEY TIMER RELAY to
turn off the servo contactor (MC). Set time of the delay more than deceleration
time of axes. (Approx. 3 [sec])
7)
When the servo contactor external control input (P24V - PONI) on the servo
power supply unit is not used, short P24V and PONI by wiring.
– 111 –