Alarm Relay Priorities - Danfoss AK-CC55 Water Loop User Manual

Case controller for semi plug-in
Hide thumbs Also See for AK-CC55 Water Loop:
Table of Contents

Advertisement

AK-CC55 Water Loop
Function
Description
Display readout ad-
Correction of the display´s temperature.If the temper-
justment
ature at the products and the temperature received
by the controller are not identical, an offset adjust-
ment of the display temperature can be carried out.
Temperature unit
Select whether temperatures are to be shown as °C or
as °F.
Display keyboard
With this setting it is possible to lock the keyboard
lock
operation of the local display.
None: Display keyboard operation will never be
locked.
Local: When not used for some time, the local display
will lock the keyboard operations and a special key
combination is required in order to enable the key-
board operations.
Network: When the controller receives a master con-
trol signal (--- Key/BT lock) via the network, the dis-
play keyboard operations will be locked. The key-
board operations can only be activated again by set-
ting the master control signal OFF via the System
Manager.

Alarm relay priorities

Table 31: Alarm relay priorities
Function
Description
Alarm relay
Actual status of output function
Alarm relay priority
Set which alarm priorities that are to activate the
alarm relay: 0=Not used, alarm relay is not used1:
High. Alarm with high priority will activate relay2: Me-
dium. Alarms with high or medium priority will acti-
vate the alarm relay3: All. All alarms will activate alarm
relay
Mute alarm
When muting alarms, the alarm relay will stop signal-
ling the alarm until a new alarm arises
High temperature -
Select the priority of the alarms assigned to the alarm
Priority
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
Low temperature -
Select the priority of the alarms assigned to the alarm
Priority
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
Sensor errors - Prior-
Select the priority of the alarms assigned to the alarm
ity
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
DI alarms - Priority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
Defrost - Priority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
Miscellaneous - Pri-
Select the priority of the alarms assigned to the alarm
ority
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
Control stopped -
Select the priority of the alarms assigned to the alarm
Priority
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
© Danfoss | Climate Solutions | 2022.04
Values
0=Celsius, 1=Fahrenheit
0=None, 1=Local, 2=Network
Values
0=OFF, 1=ON
0=Not used, 1=High Priority, 2=Medium priority,
3=All
0=OFF, 1=ON
0=Disabled, 3=Low, 2=Medium, 1=High
0=Disabled, 3=Low, 2=Medium, 1=High
0=Disabled, 3=Low, 2=Medium, 1=High
0=Disabled, 3=Low, 2=Medium, 1=High
0=Disabled, 3=Low, 2=Medium, 1=High
0=Disabled, 3=Low, 2=Medium, 1=High
0=Disabled, 3=Low, 2=Medium, 1=High
Code
Short name
r04
r04 Disp. Adj. K
r05
r05 Temp.unit
P89
P89 LockDispKey
Code
Short name
u62
u62 Alarm relay
P41
P41 Al.Rel.Prio
q38
q38 Mute Alarm
q28
q28 Hi Temp Prio
q29
q29 Lo Temp Prio
q30
q30 Sensor Prio
q31
q31 DIAlarm Prio
q32
q32 Defrost Prio
q33
q33 Misc Prio
q35
q35 CtrlOFF Prio
BC378540472015en-000101 | 58