Compressor/Pump Control - Danfoss AK-CC55 Water Loop User Manual

Case controller for semi plug-in
Hide thumbs Also See for AK-CC55 Water Loop:
Table of Contents

Advertisement

AK-CC55 Water Loop
Function
Description
Def. start 6 - Hours
Time in hours for start of defrost
Def. start 6 - Minutes Time in minutes for when defrost cycle is to be star-
ted
Monday - Follow
schedule
Tuesday - Follow
schedule
Wednesday - Follow
schedule
Thursday - Follow
schedule
Friday - Follow
schedule
Saturday - Follow
schedule
Sunday - Follow
schedule

Compressor/Pump control

Table 25: Compressor/Pump control
Function
Description
Control state A
Readout of the actual control state of the controller
Thermostat air
Thermostat temperature
temp. A
Thermostat cut-in
Readout of the actual cut-in value for the thermostat
temp.
Thermostat cut-out
Readout of the actual cut-out value for the thermo-
temp.
stat
Compressor 1
Actual status of output function
Compressor 2
Actual status of output function
Compressor speed
Actual status of output function
Brine pump
Actual status of output function
Brine pump speed
Actual status of output function
S7 Brine inlet temp.
Actual sensor value
S8 Brine outlet
Actual sensor value
temp.
Min ON time
Minimum time the compressor is to run once it has
been started.
Min OFF time
Minimum time the compressor has to be stopped
Delay between
Time delay for couplings of two compressors. The
comp.
step delay is the time that has to elapse from the first
compressor cuts in and until the next compressor can
cut in.
Step control mode
Selection of step control mode for compressors. At se-
quential mode compressor 1 will always be the first to
start and the last to stop. In cyclic mode the run time
between the compressor will be equalized.
Comp. 2 ctrl. Th.
Select whether compressor 2 is to be in operation in
band 2
thermostat band 2
Min. speed
The minimum allowed speed
Start speed
The requested start speed (must be set to a higher
value than "Min. speed"). After start, this speed is
maintained for 10 seconds before speed control is
started
Max. speed
The maximum allowed speed
Comp. defrost speed The compressor will run with the defined speed dur-
ing the hot gas defrost
Max. speed slope
Limitation on how fast the speed can ramp up/down
(set in % per. second)
© Danfoss | Climate Solutions | 2022.04
Values
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes
Values
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip off, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 17=Door open, 18=Melt
period, 19=Modulating temp. control, 20=Emergency
control, 25=Manual control, 29=Case cleaning,
30=Forced cooling, 32=Power-up delay, 33=Air heat-
ing, 34=Comp. safety cut-out, 45=Shut down control-
ler, 50=High S7 Brine inlet
0=OFF, 1=ON
0=OFF, 1=ON
0=OFF, 1=ON
1=Sequential, 2=Cyclic
0=OFF, 1=ON
Code
Short name
t06
t06 Def. 6 hr.
t16
t16 Def. 6 min.
t51
t51 Mon.Schedule
t52
t52 Tue.Schedule
t53
t53 Wed.Schedule
t54
t54 Thu.Schedule
t55
t55 Fri.Schedule
t56
t56 Sat.Schedule
t57
t57 Sun.Schedule
Code
Short name
u00
u00 Ctrl. state
u17
u17 Ther. air
u90
u90 Cutin temp.
u91
u91 Cutout temp.
u58
u58 Comp1/LLSV
u67
u67 Comp2 relay
u52
u52 Comp. Cap.
U17
U17 Brine pump
U28
U28 Pump speed
u98
u98 S7 temp
u93
u93 S8 temp
c01
c01 Min. On time
c02
c02 Min.Off time
c05
c05 Step delay
c08
c08 Step mode
c85
c85 Cmp2 In Th2
c46
c46 Min speed
c47
c47 Start speed
c48
c48 Max speed
c97
c97 DefrostSpeed
c96
c96 MaxSlopeRate
BC378540472015en-000101 | 54