AK-CC55 Water Loop
Function
Description
DI2 Configuration
Select the function of the digital input
Temperature sensor
Sensor type for S3, S4 and S5. Normally a Pt 1000 sen-
type
sor with great signal accuracy is used. But you can al-
so use a sensor with another signal accuracy. That
could e.g. be a PTC sensor (1000 ohm at 25 °C). All the
mounted sensors S3-S5 must be of the same type.
Sensor point 1 - Temp.
Sensor point 1 - kohm
Sensor point 1 - ohm
Sensor point 2 - Temp.
Sensor point 2 - kohm
Sensor point 2 - ohm
Sensor point 3 - Temp.
Sensor point 3 - kohm
Sensor point 3 - ohm
Defrost method
Select method of defrost
Defrost stop meth-
Here you define whether a defrost cycle is to be stop-
od
ped by time or by a temperature sensor
Defrost stop limit A
When the selected defrost stop sensor reaches the set
limit, the defrost cycle is terminated
Food type
When changing the food type the controller will auto-
matically adapt temperature setpoints and alarm lim-
its according to the selected food type. Please be
aware that the setting will revert to "None" after hav-
ing been changed.
Food temp. sensor
Select the temperature to be used for the food tem-
perature representation
Network address
Network address of the controller
DO1 Function
Function associated to the physical input/output
DO2 Function
Function associated to the physical input/output
DO3 Function
Function associated to the physical input/output
DO4 Function
Function associated to the physical input/output
DO5 Function
Function associated to the physical input/output
DI1 Function
Function associated to the physical input/output
DI2 Function
Function associated to the physical input/output
AI1 Function
Function associated to the physical input/output
AI2 Function
Function associated to the physical input/output
AI3 Function
Function associated to the physical input/output
AI4 Function
Function associated to the physical input/output
AI5 Function
Function associated to the physical input/output
AO1 Function
Function associated to the physical input/output
© Danfoss | Climate Solutions | 2022.04
Values
0=None, 1=DI status, 2=Door function, 3=Door alarm,
4=Defrost start, 5=Main switch, 6=Night setback,
7=Thermostat band, 8=Alarm at closed, 9=Alarm at
open, 10=Case cleaning, 11=Forced cooling,
12=Open blinds, 13=Coordinated defrost, 15=Shut-
down, 16=Light control, 20=Leak detection,
24=Comp. safety, 25=Speed drive alarm, 26=Force
cond. fan ON, 29=Door fan stop
0=Pt 1000, 1=PTC 1000, 2=NTC 5k, 3=NTC 10k,
4=User-defined
The temperature value for the user-defined tempera-
ture sensor in the reference point
The resistance value in kohm for the user-defined
temperature sensor in the reference point
The resistance value in ohm for the user-defined tem-
perature sensor in the reference point
The temperature value for the user-defined tempera-
ture sensor in the reference point
The resistance value in kohm for the user-defined
temperature sensor in the reference point
The resistance value in ohm for the user-defined tem-
perature sensor in the reference point
The temperature value for the user-defined tempera-
ture sensor in the reference point
The resistance value in kohm for the user-defined
temperature sensor in the reference point
The resistance value in ohm for the user-defined tem-
perature sensor in the reference point
0=None, 1=Electrical, 2=Hot gas, 4=Air/Offcycle
0=Time, 1=S5 sensor, 2=S4 sensor
0=None, 1=Vegetables, 2=Dairy, 3=Meat and fish,
4=Frozen food, 5=Ice cream
1=Thermostat air, 2=Alarm air, 3=S3 Air ON evap.
Code
Short name
o37
o37 DI2 Config.
o06
o06 SensorConfig
X20
--- SP1 Temp
X21
--- SP1 kohm
X22
--- SP1 ohm
X23
--- SP2 Temp
X24
--- SP2 kohm
X25
--- SP2 ohm
X26
--- SP3 Temp
X27
--- SP3 kohm
X28
--- SP3 ohm
d01
d01 Def. method
d10
d10 DefStopSens.
d02
d02 Def.StopTemp
r89
r89 Food type
q39
q39 Food sensor
o03
o03 Unit addr.
U61
U61 DO1 Config.
U62
U62 DO2 Config.
U63
U63 DO3 Config.
U64
U64 DO4 Config.
U65
U65 DO5 Config.
Y55
DI1 Config
Y56
DI2 Config
Y58
AI1 Config
Y59
AI2 Config
Y60
AI3 Config
Y61
AI4 Config
Y62
AI5 Config
U69
U69 AO1 Config.