Configuration - continued
Set alarm priorities
1. Go to Configuration menu
2. Select Alarm priorities
3. Set priorities for Suction group
Press the +-button to go on to the next page
4. Set alarm priorities for condenser
AK-PC 772A
Capacity controller RS8HF102 © Danfoss 2017-07
Very many functions have an alarm connected.
Your choice of functions and settings has connected all the relevant
alarms that are current. They will be shown with text in the three
pictures.
All alarms that can occur can be set for a given order of priority:
• "High" is the most important one
• "Log only" has lowest priority
• "Disconnected" gives no action
The interdependence between setting and action can be seen in the
table.
Log
Alarm relay selection
Setting
Non
High
X
X
Medium
X
Low
X
Log only
X
Discon-
nected
See also alarm text at the end of the manual.
In our example we select the settings shown here in the display
Net-
AKM-
work
dest.
High
Low - High
X
X
X
X
X
X
1
2
3
4
73