Danfoss AK-CC55 Water Loop User Manual page 39

Case controller for semi plug-in
Hide thumbs Also See for AK-CC55 Water Loop:
Table of Contents

Advertisement

AK-CC55 Water Loop
5.
For network. Set the address in o03
6.
Then select a set of presets from the "Food type" help table
7.
Open parameter r89 and set the number for the array of presettings. The few selected settings will now be
transferred to the menu
8.
Set the desired cut-out temperature r00
9.
Set the weighted thermostat air temperature between S4 and S3 sensor r15
10.
Set the weighted thermostat air temperature between S4 and S3 during night operation r61
11.
Set the weighted alarm air temperature between S4 and S3 A36
12.
Set the weighted display readout between S4 and S3 o17
13.
Set the desired defrost method in d01
14.
Set the interval time between defrost starts in d03
15.
Set the desired defrost sensor in d10
16.
Set the maximum defrost time in d04
17.
Set the defrost stop temperature in d02
18.
Open parameter r12 and start the regulation
19.
Go through the parameter list and change the factory values where needed
20.
Get the controller up and running on network:
◦ MODBUS: Activate scan function in system unit
Table 8: Food type settings
Setting of presettings (r89).
After setting 1-5, setting is returned to 0.
Food type
Temperature (r00)
Max. temp. setting (r02)
Min. temp. setting (r03)
Upper alarm limit (A13)
Lower alarm limit (A14)
Upper alarm limit for S6 (A22)
Lower alarm limit for S6 (A23)
© Danfoss | Climate Solutions | 2022.04
1
2
Vegetables
Milk
8 °C
0 °C
10 °C
4 °C
4 °C
-4 °C
14 °C
8 °C
0 °C
-5 °C
14 °C
8 °C
0 °C
-5 °C
3
4
Meat/fish
Frozen food
-2 °C
-20 °C
2 °C
-16 °C
-6 °C
-24 °C
8 °C
-15 °C
-5 °C
-30 °C
8 °C
-15 °C
-5 °C
-30 °C
BC378540472015en-000101 | 39
5
Ice cream
-24 °C
-20 °C
-28 °C
-15 °C
-30 °C
-15 °C
-30 °C