Technical Data - Gira One 5062 00 Operating Instructions Manual

Switching actuator 2-gang / blind actuator, 1-gang 16 a with binary input, 3-gang
Table of Contents

Advertisement

Switching actuator 2-gang / blind actuator, 1-gang 16 A with binary input, 3-gang
Switch on the bus voltage or connect the bus again at the device. Release the
programming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.
Deactivating safe-state mode
Switch off the bus voltage (wait approx. 10 s) or carry out programming.
Master reset
The master reset restores the basic device settings (firmware remains in place). The
device must then be recommissioned with the GPA.
Performing a master reset
Precondition: The safe-state mode is activated.
Press and hold down the programming button for > 5 s.
The programming LED flashes quickly.
The device performs a master reset, restarts and is ready for operation again
after approx. 5 s.
5

Technical data

Rated voltage
Current consumption
Connection mode
Outputs
Connection mode
Switching voltage
Switching current per device
Fluorescent lamps
Switch-on current 200 μs
Switch-on current 20 ms
Power consumption per output
Ohmic load
Capacitive load
Motors
Incandescent lamps
HV halogen lamps
HV-LED lamps
82404232
29.11.2022
DC 21 ... 32 V SELV
Device connection terminal on control
max. 16 A (140 μF)
5 ... 18 mA
cable
Screw terminals
AC 250 V ~
Σ 16 A
Σ 16 AX
max. 800 A
max. 165 A
2500 W
1380 VA
2300 W
2300 W
max. 400 W
11 / 17