Switching actuator / blind actuator 16 A Standard & Komfort
■
Press and hold down the programming button for > 5 s.
The programming LED flashes quickly.
The device performs a master reset, restarts and is ready for operation again after ap-
prox. 5 s.
Restoring the device to factory settings
Devices can be reset to factory settings with the Gira ETS Service App. This function uses the
firmware contained in the device that was active at the time of delivery (delivery state). Restor-
ing the factory settings causes the devices to lose their physical address and configuration.
6
Technical data
Ambient conditions
Ambient temperature
Storage/transport temperature
KNX
KNX medium
Commissioning mode
Rated voltage KNX
Current consumption KNX
Order no. 5023 00, 5028 00,
5033 00, 5038 00
Order no. 5030 00, 5040 00
Outputs
Switching voltage
Switching current AC1
Fluorescent lamps
Current carrying capacity
Neighbouring outputs
Loads per output
Ohmic load
Capacitive load
Motors
Switch-on current 200 μs
Switch-on current 20 ms
Lamp loads 230 V
Incandescent lamps
HV halogen lamps
HV-LED lamps
LV halogen lamps with electronic transformers
LV halogen lamps with inductive transformer
Fluorescent lamps T5/T8
uncompensated
parallel compensated
twin-lamp circuit
82402612
23.09.2020
-5 ... +45 °C
-25 ... +70 °C
TP256
S-mode
DC 21 ... 32 V SELV
5 ... 18 mA
5 ... 24 mA
AC 250 V ~
16 A
16 AX
Ʃ 20 A
3000 W
max. 16 A (140μ)
1380 VA
max. 800 A
max. 165 A
3000 W
2500 W
max. 400 W
1500 W
1200 VA
1000 W
1160 W (140 μF)
2300 W / 140 μF
8 / 9