Technical Data - Gira KNX 213900 Operating Instructions Manual

Heating actuator 6-gang with controller
Table of Contents

Advertisement

Heating actuator 6-gang with controller
7

Technical data

KNX
KNX medium
Commissioning mode
Rated voltage KNX
Current consumption KNX
Heating outputs
Contact type
Switching voltage
Mains frequency
Switching current
Switch-on current
Switch-on current
Number of drives per output
230 V drives
24 V drives
Housing
Installation width
Connection of outputs
Connection mode
Single stranded
Finely stranded without conductor sleeve
Finely stranded with conductor sleeve
Ambient conditions
Ambient temperature
Storage/transport temperature
Connection torque, screw terminals
82406412
29.08.2022
TP256
S-mode
DC 21 ... 32 V SELV
4.5 ... 10 mA
Semi-conductor (Triac), ε
AC 24 / 230 V ~
50 / 60 Hz
5 ... 160 mA
max. 1.5 A (2 s)
max. 0.3 A (2 min)
max. 4
max. 2
72 mm / 4 HP
Screw terminal
0.5 ... 4 mm²
0.5 ... 4 mm²
0.5 ... 2.5 mm²
-5 ... +45 °C
-25 ... +70 °C
max. 0.8 Nm
15 / 17