Switching actuator 2-gang / blind actuator, 1-gang 16 A with binary input, 3-gang
7

Parameter list

Parameters that can be set via the GPA:
Output - Switching functions
Function of the switching output
NO contact
The relay works as an NO contact. The logical switching state of the switching out-
put is not forwarded to the relay in inverted form.
Switching state = OFF ("0") -> relay contact open,
Switching state = ON ("1") -> relay contact closed.
NC contact
The relay works as an NC contact. The logical switching state of the switching output
is forwarded to the relay in inverted form.
Switching state = OFF ("0") -> relay contact closed,
Switching state = ON ("1") -> relay contact open.
Switch-on delay
This parameter is used for setting the duration of the switch-on delay.
After receipt of an ON-telegram, the time that can be configured here is started. The
lamp is switched on after the set time has elapsed.
A further ON-telegram during the switch-on delay time re-triggers the time, i.e. the
time set here is started again.
An OFF-telegram received during the ON-delay will end the delay and sets the
switching status to "OFF".
Switch-off delay
This parameter is used for setting the duration of the switch-off delay.
After receipt of an OFF-telegram, the time that can be configured here is started.
The lamp is switched off after the set time has elapsed.
A further OFF-telegram during the switch-off delay time re-triggers the time, i.e. the
time set here is started again.
An ON-telegram received during the OFF-delay will end the delay and sets the
switching status to "ON".
82404232
29.11.2022
NO contact
NC contact
0 ... 3599 s (0 ... 59:59 min)
0 ... 3599 s (0 ... 59:59 min)
13 / 17