F7 Monitor List
Parameter
Parameter Name
No.
Digital Operator Display
Frequency Reference
U1-01
Frequency Ref
Output Frequency
U1-02
Output Freq
Output Current
U1-03
Output Current
Control Method
U1-04
Control Method
Motor Speed
U1-05
Motor Speed
Output Voltage
U1-06
Output Voltage
DC Bus Voltage
U1-07
DC Bus Voltage
Output Power
U1-08
Output kWatts
Torque Reference
U1-09
Torque Reference
Input Terminal Status
U1-10
Input Term Sts
Output Terminal Status
U1-11
Output Term Sts
Table A.2 F7 Monitor List
Description
Monitor
Frequency reference (speed command) monitor when in
REMOTE mode, frequency reference (speed command)
setting location when in local mode or b1-01 = 0.
Output frequency
Output current
Control method set in A1-02.
0 = V/F without PG
1 = V/F with PG
2 = Open Loop Vector
3 = Flux Vector
Motor speed feedback
Output voltage
DC Bus Voltage
Output power
Torque reference
Input terminal status
0
0 0 0 0 0 0 0
1: FWD. run
1: REV. run
1: Multi-function input 1
1: Multi-function input 2
1: Multi-function input 3
1: Multi-function input 4
1: Multi-function input 5
1: Multi-function input 6
Output terminal status.
0 0 0 0 0 0 0 0
1: Multi-function Output 1
(Terminal M1-M2) is ON.
1: Multi-function Output 2
(Terminal M3-M4) is ON.
1: Multi-function Output 3
(Terminal M5-M6) is ON.
0: Not used
1: Fault output
(Terminal MA-MB-MC) is
ON.
Programming 189
(Terminal S1) is ON.
(Terminal S2) is ON.
(Terminal S3) is ON.
(Terminal S4) is ON.
(Terminal S5) is ON.
(Terminal S6) is ON.
(Terminal S7) is ON.
(Terminal S8) is ON.
Display Units
Set by o1-03.
Set by o1-03.
0.01A
-
Set by o1-03.
0.1Vac
1Vdc
0.1kW
0.1%
-
-