YASKAWA F7 Programming Manual page 187

Hide thumbs Also See for F7:
Table of Contents

Advertisement

Parameter
Parameter Name
No.
Digital Operator Display
Drive Node Address
H5-01
Serial Comm Adr
Communication Speed
H5-02
Selection
Serial Baud Rate
Communication Parity
H5-03
Selection
Serial Com Sel
Stopping Method After
H5-04
Communication Error
Serial Fault Sel
Communication Fault
H5-05
Detection Selection
Serial Flt Dtct
Drive Transmit Wait Time
H5-06
Transmit WaitTIM
RTS Control Selection
H5-07
RTS Control Sel
Terminal RP Pulse Train
H6-01
Input Function Selection
Pulse Input Sel
H6-02
Pulse Train Input Scaling
Pulse In Scaling
H6-03
Pulse Train Input Gain
Pulse Input Gain
H6-04
Pulse Train Input Bias
Pulse Input Bias
H6-05
Pulse Train Input Filter Time
Pulse In Filter
Terminal MP Pulse Train
H6-06
Monitor Selection
Pulse Moni Sel
H6-07
Pulse Train Monitor Scaling
Pulse Moni Scale
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Description
Serial Communications Setup
Selects Drive station node number (address) for Modbus terminals
R+, R-, S+, S-. The Drive's power must be cycled for the setting to
take effect.
Selects the baud rate for Modbus terminals R+, R-, S+ and S-. The
Drive's power must be cycled for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
Selects the communication parity for Modbus terminals R+, R-, S+
and S-. The Drive's power must be cycled for the setting to take
effect.
0: No Parity
1: Even Parity
2: Odd Parity
Selects the stopping method when a communication timeout fault
(CE) is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Enables or disables the communications timeout fault (CE).
0: Disabled - A communication loss will not cause a
communication fault.
1: Enabled - If communication is lost for more than 2 seconds, a
CE fault will occur.
Set the delay time from when the Drive receives data to when the
Drive sends data.
Enables or disables "request to send" (RTS) control:
0: Disabled - RTS is always on
1: Enabled - RTS turns on only when sending
Pulse I/O Setup
Selects the function of pulse train terminal RP.
0: Frequency reference
1: PID feedback value
2: PID setpoint value
Sets the number of pulses (in Hz) that is equal to the maximum
output frequency E1-04.
Sets the output level when the pulse train input is at 100% as a
percentage of maximum output frequency E1-04.
Sets the output level when the pulse train input is 0Hz as a
percentage of maximum output frequency E1-04.
Sets the pulse train input filter time constant in seconds.
Select the pulse train monitor output terminal MP function (value
of the
part of U1-
). See Table A2 for the list of U1
monitors.
Sets the number of output pulses when the monitor is 100% (in
Hz). Set H6-06 to 2, and H6-07 to 0, to make the pulse train
monitor output synchronous to the output frequency.
Programming 179
Control Method
Setting
Factory
V/F
Range
Setting
V/F
w/
PG
0 to 20
1F
A
Hex
0 to 4
3
A
0 to 2
0
A
0 to 3
3
A
0 to 1
1
A
5 to 65
5ms
A
0 to 1
1
A
0 to 2
0
A
1000 to
1440Hz
A
32000
0.0 to
100.0%
A
1000.0
-100.0 to
0.0%
A
100.0
0.00 to
0.10sec
A
2.00
1, 2, 5,
20, 24,
2
A
31, 36
0 to
1440Hz
A
32000
Open
Flux
Loop
Vector
Vector
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A