YASKAWA F7 Programming Manual page 190

Hide thumbs Also See for F7:
Table of Contents

Advertisement

Parameter
Parameter Name
No.
Digital Operator Display
Speed Agreement Detection
L4-01
Level
Spd Agree Level
Speed Agreement Detection
L4-02
Width
Spd Agree Width
Speed Agreement Detection
L4-03
Level (+/-)
Spd Agree Lvl +-
Speed Agreement Detection
L4-04
Width (+/-)
Spd Agree Wdth +-
Frequency Reference Loss
L4-05
Detection Selection
Ref Loss Sel
Frequency Reference Level
L4-06
at Loss Frequency
Fref at Floss
Number of Auto Restart
L5-01
Attempts
Num of Restarts
Auto Restart Operation
L5-02
Selection
Restart Sel
Denotes that parameter can be changed when the Drive is running.
*1 For Heavy Duty (HD) Rating: Setting Range=0.0 to 300.0.
*2 For Heavy Duty (HD) Rating: Setting Range= -300.0 to 300.0.
Table A.1 F7 Parameter List (Continued)
Description
Reference Detection
These parameters configure the multi-function output (H2-
settings "Fref/Fout agree 1", "Fref/Set agree 1", "Frequency
detection 1," and "Frequency detection 2". Parameter L4-01 sets
the level while parameter L4-02 sets the hysteresis for the speed
detection output function.
These parameters configure the multi-function output (H2-
settings "Fref/Fout agree 2", "Fref/Set agree 2",
"Frequency detection 3," or "Frequency detection 4". Parameter
L4-03 sets the level while parameter L4-04 sets the hysteresis for
the speed detection output function.
Determines how the Drive will react when the frequency reference
is lost. The frequency reference is considered lost when reference
drops 90% or more of its current value in less than 400ms.
0: Stop - Drive will stop.
1: Run at L4-06 PrevRef - Drive will run at the percentage set in
L4-06 of the frequency reference level at the time frequency
reference was lost.
If the frequency reference loss function is enabled (L4-05=1) and
frequency reference is lost, the Drive will run at a reduced
frequency reference determined by the following formula:
Fref = Fref at time of loss
L4-06.
*
Fault Restart
Sets the counter for the number of times the Drive will perform an
automatic restart on the following faults: GF, LF, OC, OV, PF, PUF,
RH, RR, OL1, OL2, OL3, OL4, UV1. Auto restart will check to
see if the fault has cleared every 5ms. When no fault is present, the
Drive will attempt an auto restart. If the Drive faults after an auto
restart attempt, the counter is incremented. When the Drive
operates without fault for 10 minutes, the counter will reset to the
value set in L5-01.
Determines if the fault contact activates during an automatic restart
attempt.
0: No Fault Relay - fault contact will not activate during an
automatic restart attempt.
1: Fault Relay Active - fault contact will activate during an
automatic restart attempt.
For Normal Duty (ND) Rating: Setting Range=0.0 to 400.0.
For Normal Duty (ND) Rating: Setting Range= -400.0 to 400.0.
Programming 182
Setting
Factory
Range
Setting
V/F
Varies
by
)
0.0Hz
A
Duty
1
Rating*
0.0 to
2.0Hz
A
20.0
Varies
by
)
0.0Hz
A
Duty
2
Rating*
0.0 to
2.0Hz
A
20.0
0 to 1
0
A
0 to
80.0%
A
100.0
0 to 10
0
A
0 to 1
0
A
Control Method
V/F
Open
Flux
w/
Loop
Vector
PG
Vector
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A